[Malfunction phenomenon]
guiding device“trembles”
[Examine analysis]
The system guiding the set
Sensitivity
of is high
[Solution]
Setting
Sensitivity
to the high position again
consult
:
[Malfunction phenomenon]
Guiding device does not guide the material position correctly
[Examine analysis]
The servo-drive runs to error direction and the sensor test is set erringly
[Solution]
1.
Exchange 21, 22 two connection lines.
2.
.adjust S3 to the opposite position
3.install the sensor to the opposite position
[Malfunction phenomenon]
After galvanized there are no material in the sensor
。
LED blinks on the material show window.
[Examine analysis]
Ensure no material in the sensor.
[Solution]
Use soft material and clean the lens of the sensor.
[Malfunction phenomenon]
The function of the automatic aim center does not come true.
[Examine analysis]
Press S-C and the guiding device moves to the end of the edge.
[Solution]
Exchange 14.16 two connected lines
[Malfunction phenomenon]
After galvanized the system does not run according to the former set.
[Examine analysis]
Ensure the requirement and the way of the system.
[Solution]
Run “basic set up” again.
[Malfunction phenomenon]
Power On the system cannot
Work, cannot display or No display
[Examine analysis]
Affirm DC24V Power Supply No wrong
[Solution]
]
1.Power Supply again ON
2.Press System reset Key